Produktinfos

Type EV

Single-phase-transformers variable according to EN 61558 (VDE 0550, 0551, EN 60742) 80 VA to 1600 VA

Properties

  • Single Plate stack lamination,
  • vacuum impregnated,
  • resin impregnated class F,
  • not welded,
  • low power losses,
  • max. ambient temperature 40°C,
  • insulation class E,
  • protection system IP 00,
  • Frequency 50 – 60 Hz,
  • Screw according to VBG4 and VDE 106
  • „finger security“
  • Voltages on customer’s request

Designs of Product

Control-transformer

Isolating-transformer

Safety-transformer

In addition to all possible designs:

UL-approval

Technical data / Dimensions in mm

Type Power (VA) Bestell-Nr. a b c d e f Total Weight (kg)
EV 80 80 004 001 0000 84 103 89 64 61 5 x 9 2,2
EV 100 100 004 002 0000 84 103 89 64 61 5 x 9 2,2
EV 160 160 004 003 0000 96 108 100 84 71 6 x 11 2,8
EV 250 250 004 004 0000 96 120 100 84 84 6 x 11 3,6
EV 320 320 004 005 0000 120 105 120 90 69 6 x 11 4,4
EV 400 400 004 006 0000 120 110 120 90 81 6 x 11 5,3
EV 500 500 004 007 0000 120 130 120 90 101 6 x 11 6,8
EV 630 630 004 008 0000 150 112 160 122 84 7 x 12 8
EV 800 800 004 009 0000 150 130 152 122 101 7 x 12 10,5
EV 1000 1000 004 010 0000 150 146 152 122 127 7 x 12 13,4
EV 1250 1250 004 011 0000 150 146 152 122 127 7 x 12 13,5
EV 1600 1600 004 012 0000 174 162 155 125 138 8 x 14 15,5
EV 2000 2000 004 013 0000 174 162 155 125 138 8 x 14 16,8
EV 2500 2500 004 014 0000 192 152 175 150 123 10 x 17 21,0

Dimension c: The terminal sizes varies correlative to the currents.

The total height varies due to the bridges up to + 20 mm.

The company reserves the right to alter specifications without prior notice.

Wiring Diagram

Primary connection 1 + 2

Primary Voltages Bridge Wiring
210 V 1 + 9  und  2 + 3
230 V 1 + 8  und  2 + 4
250 V 1 + 7  und  2 + 5
380 V 3 + 10
400 V 4 + 10
420 V 3 + 9
440 V 4 + 9
460 V 5 + 9
480 V 5 + 8
500 V 5 + 7
530 V 6 + 8
550 V 6 + 7